Skip to main content
Schneider Electric C10B4TM025 — Miniature Circuit Breakers (MCB)

Schneider Electric C10B4TM025 ComPacT NSX100B, 25 A, 40 kA I

MPNC10B4TM025
Active

Schneider Electric ComPacT NSX100B, C10B4TM025, 25 A thermal-magnetic circuit breaker, 4P, 40 kA Icu at 240 V AC, IP40.

$176.63 – $517.86Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10B4TM025 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B4TM025 — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B4TM025 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B4TM025 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10B4TM025 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B4TM025 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B4TM025 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C10B4TM025 is a ComPacT NSX100B circuit breaker with a 25 A thermal-magnetic TM-D trip unit, 4 poles, and a breaking capacity of 40 kA Icu at 220/240 V AC 50/60 Hz per EN/IEC 60947-2. It is rated Category A (no intentional short-time delay) and suitable for isolation per EN/IEC 60947-2 — meaning you can use it as a disconnecting means for the downstream circuit.

Mounts on a backplate (not DIN rail), in horizontal or vertical orientation, flat on the back. Front connections on both line and load sides — no rear-access required, which simplifies panel layout. The 35 mm connection pitch matches standard busbar systems. IP40 enclosure protection keeps dust out; IK07 impact resistance handles incidental tool drops during commissioning.

Frequently asked questions

What is the breaking capacity of C10B4TM025 at 415 V?

The breaking capacity is 25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What compliance standards does C10B4TM025 meet?

It is certified to EN/IEC 60947-2, with IP40 per IEC 60529, IK07 per IEC 62262, and pollution degree 3 per IEC 60664-1.

Where can I buy C10B4TM025 and how is it quoted?

The C10B4TM025 is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
C10B4TM025