Schneider Electric C10B4TM063 — Miniature Circuit Breakers (MCB)

Schneider Electric C10B4TM063 ComPacT NSX 63A 4P MCCB, 25 kA

MPNC10B4TM063
Active

Schneider Electric ComPacT NSX, NSX100B, circuit breaker, 4P, 63 A at 40 °C, TM-D trip unit, 25 kA Icu at 415 V AC 50/60 Hz, EN/IEC 60947-2.

$178.24 – $530.28Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10B4TM063 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B4TM063 — Ratings
ParameterValue
Rated current (In)63 A at 40 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B4TM063 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B4TM063 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10B4TM063 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B4TM063 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B4TM063 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The magnetic (I) element handles short-circuit protection, and the thermal (L) element handles overloads, so the trip unit is self-contained: no external relay needed for standard distribution. At 415 V AC, the Icu is 25 kA; at 440 V it drops to 20 kA, and at 500 V to 15 kA. The 25 kA code 'B' in the order code indicates the 415 V rating is the design target.

Mounts on a backplate in any orientation — horizontal or vertical, flat against the back. The 140 mm width, 161 mm height, and 86 mm depth fit standard distribution panel layouts. IP40 front face and IK07 impact resistance are adequate for indoor panel mounting where tools or dropped parts might strike the breaker. Not rated for washdown — keep it behind a sealed enclosure door if the environment is wet or dusty.

Frequently asked questions

What is the breaking capacity of C10B4TM063 at 415 V?

25 kA Icu at 380/415 V AC 50/60 Hz per EN/IEC 60947-2. At 440 V it drops to 20 kA, and at 500 V to 15 kA.

What trip unit does C10B4TM063 use?

A TM-D thermal-magnetic trip unit. The thermal element (L) protects against overloads; the magnetic element (I) protects against short-circuits. No earth-leakage protection is built in.

MPN
C10B4TM063