Skip to main content
Schneider Electric C10B4TM080 — Miniature Circuit Breakers (MCB)

Schneider Electric C10B4TM080 ComPacT NSX100B, 80 A, 25 kA 4

MPNC10B4TM080
Active

Schneider Electric ComPacT NSX series, NSX100B, 4-pole circuit breaker, 80 A thermal-magnetic TM-D trip unit, 25 kA Icu at 415 V AC, toggle control.

$194.71 – $542.59Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10B4TM080 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B4TM080 — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B4TM080 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B4TM080 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10B4TM080 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B4TM080 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B4TM080 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

80 A thermal-magnetic breaker for distribution panels

The breaking capacity reaches 25 kA Icu at 380/415 V AC, 20 kA at 440 V, and 15 kA at 500 V — enough headroom for most commercial and light industrial panelboards.

The 80 A frame is sized for feeder or large branch circuits; the TM-D trip curve gives a fixed magnetic pickup that coordinates with downstream MCBs. Pollution degree 3 (IEC 60664-1) means it tolerates conductive dust in unsealed enclosures — typical for IP40-rated distribution boards. The 50,000-cycle mechanical endurance and 30,000-cycle electrical endurance at 440 V In suit it for frequent switching in machine-tool or HVAC control panels.

IP40 front face and IK07 impact resistance suit it for enclosed panel installations where occasional tool contact is expected.

Frequently asked questions

Where can I buy C10B4TM080 and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of C10B4TM080 at 415 V?

25 kA Icu at 380/415 V AC, 50/60 Hz, conforming to IEC 60947-2. At 440 V it is 20 kA, and at 500 V it is 15 kA.

What standards does C10B4TM080 comply with?

It is designed and tested to EN/IEC 60947-2 for circuit-breaker performance, with suitability for isolation per that standard. Pollution degree 3 per IEC 60664-1 and overvoltage category III are also specified.

MPN