Skip to main content
Schneider Electric C10B4TM040C — Miniature Circuit Breakers (MCB)

Schneider Electric C10B4TM040C ComPacT NSX100B, 40 A, 4P, 25

MPNC10B4TM040C
Active

Schneider Electric ComPacT NSX, NSX100B, circuit breaker, 40 A, TM-D trip unit, 4P, 25 kA Icu at 415 V AC, toggle control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10B4TM040C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B4TM040C — Ratings
ParameterValue
Rated current (In)40 A at 50 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B4TM040C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B4TM040C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10B4TM040C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B4TM040C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B4TM040C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It carries a 40 A thermal-magnetic TM-D trip unit that provides L (overload, thermal) and I (short-circuit, magnetic) protection — the thermal element handles sustained overloads; the magnetic element clears hard faults fast. At 220/240 V AC the C10B4TM040C interrupts 40 kA Icu; at 380/415 V AC that figure is 25 kA Icu; at 440 V AC it's 20 kA Icu; and at 500 V AC it's 15 kA Icu, all per IEC 60947-2. For a 400 V panel fed by a transformer with typical available fault current in the 18–22 kA range, the 25 kA rating at 415 V gives solid headroom — you're not riding the edge of the curve.

Backplate-mounted with front-facing connections top and bottom. Mounts horizontally or vertically flat on the backplate; the toggle stays accessible either way.

IK07 impact resistance means it handles a 2 J tool drop without cracking the case. Operating altitude is 0–2000 m at full rating; derate above that up to 5000 m.

Durability and electrical life

Mechanical endurance is 50,000 cycles. Electrical durability depends on the load: 50,000 cycles at 440 V at half rated current (In/2), 30,000 cycles at full In, 20,000 cycles at 690 V In/2, and 10,000 cycles at 690 V In. For a breaker that mostly sees infrequent switching (panel feeder, not a motor-starting contactor), that's more than adequate — you'll retire the panel before you hit those numbers.

Frequently asked questions

What is the breaking capacity of this breaker at 415 V?

25 kA Icu at 380/415 V AC per IEC 60947-2. That's the rating that governs most 400 V-class industrial panels.

What trip unit does the C10B4TM040C use?

A 40 A thermal-magnetic TM-D unit. The thermal element provides overload protection (L), and the magnetic element provides short-circuit protection (I).

Where can I buy the C10B4TM040C and how is it quoted?

We source the C10B4TM040C to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance documentation is available for this breaker?

The breaker is certified to EN/IEC 60947-2 and carries suitability for isolation per that standard. IP40 and IK07 ratings are per IEC 60529 and IEC 62262 respectively. Specific RoHS/REACH declarations are available from the manufacturer on request.

MPN
C10B4TM040C