Skip to main content
Schneider Electric C10B4TM080C — Miniature Circuit Breakers (MCB)

Schneider Electric C10B4TM080C ComPacT NSX 80 A 4P MCCB, 25

MPNC10B4TM080C
Active

Schneider Electric, ComPacT NSX, MCCB, C10B4TM080C, 80 A, 4P, 25 kA Icu at 415 V AC, thermal-magnetic TM-D trip unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10B4TM080C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B4TM080C — Ratings
ParameterValue
Rated current (In)80 A at 50 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B4TM080C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B4TM080C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10B4TM080C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B4TM080C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B4TM080C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It is a 4-pole device (4P) with a breaking capacity of 25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2 — that is the fault current it can safely interrupt at typical three-phase distribution voltages without welding contacts or venting plasma. For higher fault levels, the NSX family offers S (36 kA) and H (50 kA) variants, but for a typical 415 V line feeding motor control centers or lighting panels, the B rating covers the majority of installations.

The toggle control and front-facing connections (upside and downside) simplify wiring in a distribution board. IP40 front face keeps tools and fingers out; IK07 impact resistance handles incidental knocks during commissioning.

Frequently asked questions

What is the breaking capacity of C10B4TM080C at 415 V?

25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 440 V it drops to 20 kA Icu; at 500 V to 15 kA Icu.

Where can I buy C10B4TM080C and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

What compliance documentation does Schneider provide for C10B4TM080C?

The MCCB is certified to EN/IEC 60947-2 and carries suitability for isolation per that standard. Pollution degree 3 per IEC 60664-1. The manufacturer typically provides a Declaration of Performance and CE/UKCA marking; specific RoHS/REACH declarations are available on request from the distributor.

MPN
C10B4TM080C