It's a Category A breaker, meaning it's not intended for selectivity under short-circuit conditions; use it as a main or feeder breaker where coordination is managed upstream. The breaking capacity (Icu) varies with line voltage: 40 kA at 240 V AC, 25 kA at 415 V AC, 20 kA at 440 V AC, and 15 kA at 500 V AC. The breaker also carries an IK07 impact rating and IP40 finger protection — fine for a dry indoor enclosure, but not for washdown areas.
Mounts on a backplate in horizontal or vertical orientation. Front connections top and bottom; neutral on the left. Depth is 86 mm, width 140 mm, height 161 mm — standard for a 160 A frame NSX breaker.