No earth-leakage module fitted — this is a straight feeder or branch breaker, not a residual-current device.
Breaking capacity steps down with voltage: 40 kA Icu at 240 V, 25 kA at 415 V, 20 kA at 440 V, 15 kA at 500 V. It's Category A (no intentional short-time delay), so it trips instantaneously on magnetic pickup — coordination with downstream devices depends on that fast reaction. The 4-pole version with neutral left and no neutral protection (3D setting) means the neutral is switched but not monitored; fine for balanced loads where the neutral won't see fault current.
Front connections top and bottom — standard for panel wiring. IK07 impact rating means it survives the odd dropped tool during commissioning.
It's a standard catalogue item in the ComPacT NSX family, widely specified.