Skip to main content
Schneider Electric C10B6TM050 — Miniature Circuit Breakers (MCB)

Schneider Electric C10B6TM050 ComPacT NSX 50A 4P Circuit Bre

MPNC10B6TM050
Active

Schneider Electric ComPacT NSX, circuit breaker, 50 A, 4P, TM-D trip unit, 25 kA at 415 V AC, IP40, toggle control.

$161.73Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10B6TM050 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B6TM050 — Ratings
ParameterValue
Rated current (In)50 A at 40 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B6TM050 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B6TM050 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10B6TM050 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B6TM050 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B6TM050 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10B6TM050 is a Schneider Electric ComPacT NSX100B circuit breaker with a 50 A thermal-magnetic TM-D trip unit, 4 poles, and a 25 kA breaking capacity at 415 V AC (Icu per IEC 60947-2). The thermal-magnetic trip gives you L (overload) and I (short-circuit) protection in one unit; no separate relay to wire. At 50 A and 40 °C ambient, it's a straight fit for a 50 A feeder or a moderate motor branch circuit, though motor starting duty needs a check on the magnetic pickup vs inrush.

Mounts on a backplate — flat on the back, horizontal or vertical orientation — with front connections top and bottom. Neutral is on the left; the toggle control is manual, no motor operator by default.

Frequently asked questions

What is C10B6TM050's breaking capacity at 415 V?

25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. At 220/240 V it reaches 40 kA Icu; at 440 V it drops to 20 kA Icu.

What compliance documentation does this brand provide for C10B6TM050?

The breaker carries EN/IEC 60947-2 certification, suitability for isolation per that standard, and IP40 / IK07 mechanical impact protection. Pollution degree 3 per IEC 60664-1, overvoltage category III. Specific RoHS/REACH/UL declarations would be confirmed at quote time through the supply channel.

Where can I buy C10B6TM050 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote — no stock count or price is published here.