The C10B6TM050 is a Schneider Electric ComPacT NSX100B circuit breaker with a 50 A thermal-magnetic TM-D trip unit, 4 poles, and a 25 kA breaking capacity at 415 V AC (Icu per IEC 60947-2). The thermal-magnetic trip gives you L (overload) and I (short-circuit) protection in one unit; no separate relay to wire. At 50 A and 40 °C ambient, it's a straight fit for a 50 A feeder or a moderate motor branch circuit, though motor starting duty needs a check on the magnetic pickup vs inrush.
Mounts on a backplate — flat on the back, horizontal or vertical orientation — with front connections top and bottom. Neutral is on the left; the toggle control is manual, no motor operator by default.