Breaking capacity is 25 kA Icu at 380/415 V AC, 20 kA at 440 V, and 15 kA at 500 V. Four poles (4P), with neutral on the left and neutral protection set to 3D (no protection) per. That means the neutral pole is switched but not protected — it opens and closes with the phases but does not trip on overload or short. If you need neutral protection, this isn't the variant; look for a 4D or 3D+ setting on a different trip unit.
The 140 mm width, 161 mm height, and 86 mm depth mean it fits standard MCCB cutouts in distribution boards. Front connections top and bottom, with a 35 mm connection pitch for busbar or cable lugs.
Electrical durability: 50,000 cycles at 440 V at half rated current, 30,000 cycles at full rated current. Mechanical durability is 50,000 cycles. That gives a solid service life for distribution duty where the breaker is operated infrequently — not a daily-switching load-break device.