The C10B6TM100 is a Schneider Electric ComPacT NSX100B 4-pole thermal-magnetic circuit breaker with a TM-D trip unit rated 100 A at 40 °C. The toggle control and front-facing connections suit panel-mount installations on a backplate, mountable horizontally or vertically. The IP40 enclosure and IK07 impact rating cover indoor panel use where occasional contact is expected, not washdown environments.
Breaking capacity and selectivity coordination
The 100 A frame delivers 40 kA Icu at 240 V AC, 25 kA at 415 V AC, 20 kA at 440 V AC, and 15 kA at 500 V AC.
Trip unit and protection characteristics
The TM-D trip unit provides thermal overload protection (L) via a bimetal element and magnetic short-circuit protection (I) via a solenoid. The thermal curve is fixed, not adjustable, which simplifies coordination but limits flexibility if the load profile changes. The neutral protection setting is no protection (3D), meaning the solid neutral is not switched or monitored — confirm this matches the distribution scheme before specifying.