At 380/415 V AC it still holds 36 kA Icu, which covers standard European 400 V panelboards. The TM-D trip gives thermal overload (L) and magnetic short-circuit (I) protection; no earth-leakage module on this variant. Rated 32 A at 50 °C, so in a 40 °C panel it has headroom — no derating worry for most industrial enclosures. The 50,000-cycle mechanical endurance and 30,000-cycle electrical endurance at 440 V In give a realistic service life for a main feeder or large motor branch circuit that cycles a few times a day.
Mounts flat on a backplate — the 105 mm width, 161 mm height, 86 mm depth footprint fits standard MCCB cutouts. Front-front connections (both line and load) simplify busbar or cable routing in a distribution panel. The toggle handle gives local manual operation; IP40 front protection means tools or fingers won't accidentally contact live parts through the cover opening.