The C10F3TM032 is a Schneider Electric ComPacT NSX100F circuit breaker with a 32 A thermal-magnetic TM-D trip unit, three poles, and a 36 kA breaking capacity at 415 V AC (Icu per IEC 60947-2). The TM-D trip unit provides thermal protection (L) for overloads and magnetic protection (I) for short circuits — a standard thermal-magnetic curve for distribution duty.
Deployment context
Mounts on a backplate (not DIN rail) in a horizontal or vertical orientation, flat against the panel. Front connections on both line and load sides simplify busbar or cable routing in a distribution board. The 50,000 mechanical and 50,000/30,000 electrical cycles (at 440 V In) give a solid service life for a distribution breaker in a panel with moderate switching duty.