Skip to main content
Schneider Electric C10F3TM080C — Miniature Circuit Breakers (MCB)

Schneider Electric C10F3TM080C ComPacT NSX100F 80A MCCB, 36k

MPNC10F3TM080C
Active

Schneider Electric ComPacT NSX, NSX100F, 80 A at 50 °C, TM-D trip unit, 3P, 36 kA Icu at 415 V AC, toggle control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10F3TM080C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10F3TM080C — Ratings
ParameterValue
Rated current (In)80 A at 50 °C
Poles configuration3P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10F3TM080C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10F3TM080C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10F3TM080C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10F3TM080C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10F3TM080C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Rated for distribution duty under EN/IEC 60947-2, category A. Suitability for isolation is confirmed to that standard.

Breaking capacity at the voltages that matter

85 kA Icu at 240 V AC, 36 kA at 415 V AC, 22 kA at 525 V AC, 8 kA at 690 V AC. The 36 kA figure governs fault-withstand for a 415 V panel.

Current-production part.

Panel-fit and mounting

Front terminals top and bottom. IP40 enclosure protection, IK07 impact rating.

Durability and thermal budget

50 000 mechanical cycles; 50 000 electrical cycles at 440 V In/2, 30 000 at full In. Power dissipation 8.77 W per pole — three poles, so roughly 26 W total through the enclosure.

Frequently asked questions

What is the breaking capacity of C10F3TM080C at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What compliance documentation does Schneider provide for C10F3TM080C?

The part is certified to EN/IEC 60947-2 and carries the IEC 60947-2 mark for suitability for isolation. Specific RoHS/REACH/UL documentation is available on request from the manufacturer.

MPN