The Schneider Electric C10H4TM032 is a ComPacT NSX100H moulded-case circuit breaker (MCCB) with a 32 A thermal-magnetic TM-D trip unit, 4 poles, and a breaking capacity code of H — 70 kA Icu at 415 V AC.
The thermal-magnetic TM-D trip gives you L (thermal overload) and I (magnetic short-circuit) protection in one block, with a fixed magnetic threshold. The 4-pole version switches all four phases, neutral on the left. Breaking capacity is the headline: 100 kA Icu at 240 V AC, 70 kA at 415 V, 65 kA at 440 V, dropping to 10 kA at 690 V.
Mounts on a backplate in horizontal or vertical orientation — no DIN rail, so it bolts into a panel cutout or onto a mounting plate. IK07 impact rating means it survives a 2 J hammer blow during installation.