Skip to main content
Schneider Electric C10H4TM016C — Miniature Circuit Breakers (MCB)

Schneider Electric C10H4TM016C ComPacT NSX100H 16A 4P MCCB,

MPNC10H4TM016C
Active

Schneider Electric ComPacT NSX NSX100H, 16 A, 4P, thermal-magnetic TM-D trip unit, 100 kA Icu at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10H4TM016C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10H4TM016C — Ratings
ParameterValue
Rated current (In)16 A at 50 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10H4TM016C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10H4TM016C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10H4TM016C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10H4TM016C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10H4TM016C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10H4TM016C is a 4-pole ComPacT NSX100H MCCB with a 16 A thermal-magnetic TM-D trip unit. At 240 V AC it delivers 100 kA Icu, so it handles high-fault service entrances without cascading upstream. The TM-D trip unit gives you fixed thermal (L) and magnetic (I) protection — no interchangeable rating plugs, no electronic adjustments. For a 16 A distribution feeder or a small motor branch circuit, that's a set-and-forget choice. The 4-pole version with neutral left and 1 x Ir neutral protection means the neutral is fully rated and switched, not just a solid link. Mounts on a backplate, not a DIN rail — the 140 mm width and 161 mm height take up a standard MCCB cutout in a panel. Front connections top and bottom simplify busbar or cable landing.

IP40 front-of-panel protection means it's fine in a general-purpose industrial enclosure; if the panel gets hosed down, you'll need a separate IP65 enclosure or a rotary handle kit that seals the front cutout. Electrical durability is 50,000 cycles at 440 V In/2 and 30,000 cycles at 440 V In — that's a lot of switching for an MCCB, reflecting the NSX design's robust mechanism. Mechanical durability is 50,000 cycles. If you're using this as a manual disconnect that gets cycled daily, those numbers give you a solid service life before contact wear becomes a concern.

Frequently asked questions

How do I get current pricing and availability for C10H4TM016C?

We source and quote this part to order against an RFQ. Availability and current pricing are confirmed at quote time through our distribution channels — submit an RFQ for a firm number.

What is the breaking capacity at 415 V AC?

70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. That's the H breaking capacity code — enough for most industrial main switchboard applications.

What compliance documentation does this brand provide for C10H4TM016C?

The breaker is certified to EN/IEC 60947-2 and carries IEC 60529 IP40 and IEC 62262 IK07 ratings. Pollution degree 3 per IEC 60664-1 and overvoltage category III are on the spec. For specific RoHS/REACH declarations, the manufacturer's product compliance page for the ComPacT NSX series provides the current declarations.

MPN
C10H4TM016C