Skip to main content
Schneider Electric C10H6TM025C — Miniature Circuit Breakers (MCB)

Schneider Electric C10H6TM025C ComPacT NSX100H, 25 A, 70 kA

MPNC10H6TM025C
Obsolete

Schneider Electric ComPacT NSX, NSX100H, circuit breaker, 4P, 25 A, TM-D trip unit, 70 kA Icu at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10H6TM025C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10H6TM025C — Ratings
ParameterValue
Rated current (In)25 A at 50 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10H6TM025C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10H6TM025C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10H6TM025C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10H6TM025C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10H6TM025C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10H6TM025C is a Schneider Electric ComPacT NSX100H circuit breaker with a 25 A thermal-magnetic TM-D trip unit, 4 poles, and an H-frame breaking capacity of 70 kA Icu at 415 V AC.

Mounts on a backplate in horizontal or vertical orientation. Front connections on both upside and downside simplify busbar and cable routing in a panel. IP40 front face and IK07 impact resistance are adequate for enclosed panel mounting; no washdown rating, so keep it inside the cabinet.

Frequently asked questions

Where can I buy C10H6TM025C?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of C10H6TM025C?

25 A rated current at 50 °C, 70 kA Icu breaking capacity at 415 V AC, 4 poles, thermal-magnetic TM-D trip unit, and suitability for isolation per IEC 60947-2.

What standards does C10H6TM025C comply with?

It complies with EN/IEC 60947-2, pollution degree 3 per IEC 60664-1, overvoltage category III, and is suitable for isolation per the same standard.

MPN