Skip to main content
Schneider Electric C10H6TM050C — Miniature Circuit Breakers (MCB)

C10H6TM050C ComPacT NSX 4P 50A Circuit Breaker, 70kA 415V

MPNC10H6TM050C
Active

Schneider Electric ComPacT NSX, NSX100H frame, 4P, 50 A thermal-magnetic MCCB, 70 kA Icu at 415 V AC, toggle control, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10H6TM050C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10H6TM050C — Ratings
ParameterValue
Rated current (In)50 A at 50 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10H6TM050C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10H6TM050C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10H6TM050C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10H6TM050C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10H6TM050C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10H6TM050C is a 4-pole ComPacT NSX100H circuit breaker with a TM-D thermal-magnetic trip unit rated 50 A at 50 °C. Rated for utilisation category A (non-delayed short-time withstand), so it's suited for distribution duty, not motor-starting applications where delayed tripping is needed for coordination with downstream starters. The 50,000-cycle mechanical durability and 30,000-cycle electrical durability at 440 V In give a solid service life for a panel that cycles regularly.

Mounts on a backplate — no DIN-rail clip, so plan for a drilled panel or a mounting adapter. The 161 x 140 x 86 mm envelope (H x W x D) fits standard MCCB cutouts. Front connections top and bottom simplify bus-bar or cable landing. Neutral position is left, and the 4-pole unit uses a 3D neutral protection setting (no protection on the neutral pole) — confirm your system's neutral earthing arrangement before wiring. Toggle control, so manual on/off and trip indication are local. IK07 impact rating means it survives a hammer blow from a tool drop.

Overvoltage category III — rated for fixed-installation distribution boards.

Frequently asked questions

How do I get current pricing and availability for C10H6TM050C?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels.

What is C10H6TM050C's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The H breaking capacity code indicates this level.

What does the TM-D trip unit protect against?

Thermal-magnetic L (overload) and I (short-circuit) protection. No earth-leakage protection is included.

What compliance documentation does Schneider provide for C10H6TM050C?

The breaker is certified to EN/IEC 60947-2. Standard documentation includes the declaration of conformity and test reports for the listed breaking capacities.

MPN
C10H6TM050C