Skip to main content
Schneider Electric C10H6TM032C — Miniature Circuit Breakers (MCB)

Schneider C10H6TM032C ComPacT NSX100H MCCB, 32 A, 100 kA

MPNC10H6TM032C
Active

Schneider Electric ComPacT NSX series, NSX100H MCCB, 4-pole, 32 A thermal-magnetic trip unit (TM-D), 100 kA Icu at 240 V AC, 70 kA at 415 V AC, IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10H6TM032C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10H6TM032C — Ratings
ParameterValue
Rated current (In)32 A at 50 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10H6TM032C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10H6TM032C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10H6TM032C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10H6TM032C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10H6TM032C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10H6TM032C is a Schneider Electric ComPacT NSX100H moulded-case circuit breaker, 4-pole, rated 32 A at 50 °C with a TM-D thermal-magnetic trip unit. The H breaking-capacity code delivers 100 kA Icu at 220/240 V AC and 70 kA at 380/415 V AC, per IEC 60947-2. This is the rating that governs fault clearance in high-fault distribution panels — at 415 V it safely interrupts 70 kA without upstream cascading.

Ratings and deployment

The breaker is pollution degree 3 rated (IEC 60664-1), meaning it tolerates conductive dust and condensation typical in industrial enclosures — not a clean-room part. The 140 mm width and 161 mm height fit standard MCCB panel cutouts; depth is 86 mm including the toggle handle. Mechanical durability is 50,000 cycles; electrical durability at 440 V In is 30,000 cycles — sufficient for most distribution applications but not for frequent motor switching (that duty calls for a contactor). The 4-pole configuration (3D + neutral no protection) suits three-phase systems where the neutral is solidly bonded and does not need overcurrent protection.

Frequently asked questions

What is C10H6TM032C's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz, conforming to IEC 60947-2.

MPN
C10H6TM032C