At 240 V AC it rises to 85 kA Icu (UL 60947-4-1), and at 690 V AC it still holds 10 kA Icu.
Pollution degree 3 (IEC 60664-1) means it tolerates conductive dust and condensation — standard for an IP40 enclosure in a non-washdown industrial hall. The IK07 impact rating confirms it survives a 2 J hammer blow to the front face. Electrical durability is 30,000 cycles at rated current 440 V In, and 50,000 mechanical cycles. Power dissipation is 8.61 W per pole — three poles total 25.8 W, which matters for heat-rise calculations in a multi-breaker enclosure.
Overvoltage category III and utilisation category A. The IP40 front face and IK07 impact rating are per IEC 60529 and IEC 62262 respectively.