Skip to main content
Schneider Electric C10N3TM016C — Miniature Circuit Breakers (MCB)

Schneider Electric C10N3TM016C ComPacT NSX100N 16A 3P MCCB,

MPNC10N3TM016C
Active

Schneider Electric ComPacT NSX100N, C10N3TM016C, 3P 16 A thermal-magnetic MCCB, 50 kA Icu at 415 V AC, toggle control, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N3TM016C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N3TM016C — Ratings
ParameterValue
Rated current (In)16 A at 50 °C
Poles configuration3P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N3TM016C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N3TM016C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N3TM016C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N3TM016C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N3TM016C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C10N3TM016C is a ComPacT NSX100N moulded-case circuit breaker, 3-pole, rated 16 A at 50 °C with a TM-D thermal-magnetic trip unit. It carries an N breaking capacity: 50 kA Icu at 380/415 V AC and 90 kA Icu at 220/240 V AC, both per IEC 60947-2. That 50 kA at 415 V gives you headroom for high-fault panelboards without cascading upstream — common in distribution switchboards and motor control centres.

If your panel runs hotter, you'll need to apply the standard thermal derating curve for the NSX frame. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection; no earth-leakage module is fitted, so if you need ground-fault, you'll add a Vigi add-on block. Mechanical durability is 50,000 cycles, electrical durability varies from 50,000 cycles at In/2 up to 10,000 cycles at In — enough for frequent switching in distribution, but not a motor-starting duty cycle.

IP40 enclosure protection, IK07 impact rating.

Frequently asked questions

What is C10N3TM016C's listed range (ComPacT) on this component line?

It belongs to the ComPacT range, specifically the ComPacT NSX series.

What is C10N3TM016C's listed depth (d) (86 mm) on this component line?

The depth is 86 mm.

MPN
C10N3TM016C