The Schneider Electric C10N3TM080 is a ComPacT NSX100N circuit breaker with a TM-D thermal-magnetic trip unit rated at 80 A at 40 °C, three poles protected (3P). It is a distribution breaker built to EN/IEC 60947-2, with a breaking capacity code of N — 50 kA Icu at 380/415 V AC 50/60 Hz, and 50 kA Icu at 480 V AC per UL 60947-4-1.
Mounts flat on a backplate (not DIN-rail), so plan for a drilled panel or a subplate with clearance for its 105 mm width × 161 mm height × 86 mm depth. Overvoltage category III suits fixed-installation distribution boards downstream of the main incoming supply. The TM-D trip unit gives you thermal (L) overload protection and magnetic (I) short-circuit protection — no ground-fault module onboard (earth-leakage protection is marked 'Without').