Skip to main content
Schneider Electric C10N3TM063C — Miniature Circuit Breakers (MCB)

Schneider C10N3TM063C ComPacT NSX100N 63A 3P MCCB, 90kA

MPNC10N3TM063C
Active

Schneider Electric ComPacT NSX NSX100N, circuit breaker, 63A, 3P, TM-D trip unit, 90 kA at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N3TM063C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N3TM063C — Ratings
ParameterValue
Rated current (In)63 A at 50 °C
Poles configuration3P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N3TM063C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N3TM063C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N3TM063C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N3TM063C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N3TM063C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

What this MCCB brings to a panel

The Schneider Electric C10N3TM063C is a ComPacT NSX100N moulded-case circuit breaker (MCCB) in the N breaking-capacity tier — 90 kA Icu at 240 V AC, 50 kA at 415 V AC, and still 10 kA at 690 V AC. That's the kind of headroom that keeps a distribution board selective when a downstream fault tries to take out the whole feeder. The 63 A TM-D trip unit gives you thermal-magnetic protection: thermal for overload (L), magnetic for short-circuit (I). No earth-leakage module here — this is a straight distribution breaker, not a residual-current device. Three poles, 3D protected, rated for isolation per IEC 60947-2. That means when you flip the toggle to off, you can work downstream without pulling a separate disconnect — the breaker itself is the safety barrier.

Mounting and integration reality

Backplate mount, front connections both top and bottom. The 105 mm width and 161 mm height fit the standard ComPacT NSX footprint. IP40 front face, IK07 impact resistance.

Current lifecycle stage — this is still an active catalogue number from Schneider.

Durability and thermal budget

Electrical durability: 50,000 cycles at 440 V at half rated current, 30,000 at full In, 20,000 at 690 V half load. Mechanical durability is 50,000 cycles. Power dissipation per pole is 8.61 W — three poles means about 26 W total heat to vent from the enclosure. Rated 63 A at 50 °C ambient. Humidity tolerance 0-95 % non-condensing. Category A utilisation — not intended for motor starting duty where the breaker cycles under high inrush daily.

Frequently asked questions

What is the breaking capacity of C10N3TM063C at 415 V?

50 kA Icu at 380/415 V AC, 50/60 Hz, conforming to IEC 60947-2.

What standards does C10N3TM063C comply with?

EN/IEC 60947-2 for circuit-breaker performance, IEC 60664-1 for pollution degree 3, IEC 60529 for IP40, and IEC 62262 for IK07 impact resistance.

Does C10N3TM063C include earth-leakage protection?

No, it is a straight distribution breaker without earth-leakage protection. The TM-D trip unit handles thermal overload and magnetic short-circuit only.

MPN
C10N3TM063C