Skip to main content
Schneider Electric C10N6TM025 — Miniature Circuit Breakers (MCB)

Schneider C10N6TM025 ComPacT NSX 25A 4P Circuit Breaker, 50

MPNC10N6TM025
Active

Schneider Electric ComPacT NSX, 25 A, 4P, thermal-magnetic trip unit TM-D, breaking capacity N (50 kA at 415 V AC), EN/IEC 60947-2.

$212.00 – $634.28Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N6TM025 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N6TM025 — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N6TM025 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N6TM025 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N6TM025 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N6TM025 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N6TM025 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The thermal element handles sustained overloads; the magnetic element responds to instantaneous fault currents. No earth-leakage protection is built in — that's a separate Vigi module if needed. Mounts on a backplate in horizontal or vertical orientation. Front connections on both line and load sides simplify busbar or cable routing in a distribution panel. The 35 mm connection pitch matches standard DIN-rail terminal blocks for auxiliary wiring.

Deployment context

Rated IP40 and IK07, so it's suited for indoor panel installation where it won't see water jets or heavy impact. The 0 to 2000 m altitude range without derating covers most sites; above 2000 m up to 5000 m requires derating per the manufacturer's guidelines. Electrical durability is 50,000 cycles at 440 V at half rated current, and 30,000 cycles at full rated current. Mechanical durability is 50,000 cycles. That's typical for a molded-case breaker used for switching and protection in distribution — not a contactor duty cycle, but fine for occasional manual switching or as a disconnect.

Frequently asked questions

What is the breaking capacity of C10N6TM025 at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. That is the N breaking capacity code.

MPN
C10N6TM025