Skip to main content
Schneider Electric C10R4TM050 — Miniature Circuit Breakers (MCB)

Schneider C10R4TM050 ComPacT NSX100R, 50 A, 4P, 200 kA Icu

MPNC10R4TM050
Obsolete

Schneider Electric ComPacT NSX, NSX100R, circuit breaker, 4P, 50 A at 40 °C, TM-D trip unit, 200 kA Icu at 415 V AC, toggle control, EN/IEC 60947-2.

$14.07Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10R4TM050 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10R4TM050 — Ratings
ParameterValue
Rated current (In)50 A at 40 °C
Poles configuration4P
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10R4TM050 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C10R4TM050 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10R4TM050 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10R4TM050 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10R4TM050 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

ComPacT NSX100R — 50 A, 4-pole, 200 kA at 415 V

The Schneider Electric C10R4TM050 is a ComPacT NSX100R circuit breaker with a 50 A thermal-magnetic TM-D trip unit, four poles, and a rated breaking capacity of 200 kA Icu at 380/415 V AC 50/60 Hz per EN/IEC 60947-2. The R breaking-capacity code means it handles high prospective fault currents typical of industrial distribution panels and transformer secondaries. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection in one unit, with the neutral protection set to 1 x Ir (4D).

Breaking capacity and isolation

Rated 200 kA Icu at 415 V AC, 80 kA at 500 V, 65 kA at 525 V, and 45 kA at 690 V — the breaker clears faults across the common industrial voltage range without upstream fusing.

IP40 enclosure protection with IK07 impact resistance. Connection pitch is 35 mm. Five accessory slots are available for auxiliary contacts, shunt trips, or undervoltage releases.

Durability and service life

Electrical durability: 20,000 cycles at 440 V at In/2, 10,000 cycles at 440 V at In, and 5,000 cycles at 690 V at In. These figures give a realistic maintenance interval for a distribution breaker that sees occasional switching, not daily motor starting.

Frequently asked questions

Where can I buy C10R4TM050 and how do I get a price?

The C10R4TM050 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ to confirm current availability and pricing.

What is the breaking capacity of C10R4TM050 at 415 V?

The C10R4TM050 has a rated breaking capacity of 200 kA Icu at 380/415 V AC 50/60 Hz per EN/IEC 60947-2.

What is the closest alternative to C10R4TM050 in the ComPacT NSX family?

Within the ComPacT NSX100R frame, the closest alternative would be a breaker with the same frame size but a different trip unit rating or breaking capacity code. The C10R4TM050 is the 50 A, 4-pole, R-breaking-capacity variant with a TM-D trip unit. A different rating or pole configuration would change the order code.

What compliance documentation does Schneider provide for C10R4TM050?

The breaker is certified to EN/IEC 60947-2. It carries IP40 and IK07 ratings per IEC 60529 and IEC 62262. Pollution degree 3 and overvoltage category III per IEC 60664-1 are documented. RoHS and REACH compliance documentation is available from Schneider Electric upon request.

MPN
C10R4TM050