Skip to main content
Schneider Electric C104TM016C — Miniature Circuit Breakers (MCB)

Schneider Electric C104TM016C ComPacT NSX TM16D Trip Unit, 1

MPNC104TM016C
Obsolete

Schneider Electric ComPacT NSX100...250, TM-D trip unit, thermal-magnetic, 16 A at 50 °C, 4 poles 4D, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C104TM016C — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NSX100...250
Product/component typeTrip unit
Device applicationDistribution
C104TM016C — Ratings
ParameterValue
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz 750 V DC
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C104TM016C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
C104TM016C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C104TM016C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C104TM016C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C104TM016C is a TM-D thermal-magnetic trip unit for the ComPacT NSX100...250 range, rated 16 A at 50 °C, 4 poles (4D), and built to EN/IEC 60947-2. It provides LI protection — thermal overload (L) and magnetic short-circuit (I) — with a fixed instantaneous pickup of 190 A and an adjustable long-time pickup from 0.7 to 1 x In.

The 16 A rating at 50 °C sets the continuous current the trip unit can carry without nuisance tripping in a warm panel — if your ambient is higher, you must derate. The 190 A fixed instantaneous pickup means magnetic trips occur at roughly 12 x In, which is typical for distribution-level short-circuit protection per EN/IEC 60947-2. The 4D protected poles (all four poles with neutral protection set to 1 x Ir) suit a 4-wire distribution system where the neutral is not fully rated.

Integration Notes

This trip unit snaps into a ComPacT NSX100...250 fixed-mount circuit breaker. The IP40 front-of-panel protection (IEC 60529) is sufficient for enclosed distribution boards but not for washdown environments.

Frequently asked questions

Where can I buy C104TM016C?

We can source and quote this obsolete trip unit to order against an RFQ. Availability and current pricing are confirmed at quote time through our independent distribution network.

What standards does C104TM016C comply with?

It is designed and tested to EN/IEC 60947-2, the standard for low-voltage switchgear and controlgear circuit breakers.

What is the trip unit rating and protection scheme?

The TM-D trip unit is rated 16 A at 50 °C, with LI protection: thermal overload (L) adjustable from 0.7 to 1 x In, and fixed magnetic short-circuit (I) pickup at 190 A.