Skip to main content
Schneider Electric C10R42D100 — Miniature Circuit Breakers (MCB)

C10R42D100 ComPacT NSX 100A 4P MCCB, 200kA 415V

MPNC10R42D100
Active

Schneider Electric ComPacT NSX NSX100R, 4-pole circuit breaker, 100 A at 40 °C, MicroLogic 2.2 electronic trip unit, 200 kA Icu at 415 V AC, EN/IEC 60947-2.

$1,647.19 – $1,978.75Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10R42D100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10R42D100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10R42D100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C10R42D100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10R42D100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10R42D100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10R42D100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSoI

Product details

The Schneider Electric C10R42D100 is a ComPacT NSX100R molded-case circuit breaker, rated 100 A at 40 °C with a MicroLogic 2.2 electronic trip unit. It is a 4-pole (4P) device, designed for distribution applications per EN/IEC 60947-2.

Trip unit and protection logic

The trip unit rating is fixed at 100 A; this is not an adjustable-frame breaker where you swap rating plugs.

The R breaking capacity code (200 kA at 415 V AC) is the headline figure, but the breaker also carries 200 kA Icu at 240 V, 200 kA at 440 V, 80 kA at 500 V, 65 kA at 525 V, and 45 kA at 690 V.

Mechanical and electrical endurance

Rated for 20,000 mechanical cycles and 20,000 electrical cycles at 440 V at rated current (In). At half-rated current (In/2) the electrical endurance doubles to 20,000 cycles at 440 V and 10,000 cycles at 690 V. For an MRO planner stocking spares for a panel that sees infrequent switching, the mechanical endurance is the limiting factor — the breaker is not designed for daily load-break duty like a contactor.

Physical integration and environment

Connection pitch is 35 mm. IP40 enclosure protection (no ingress of tools or wires >1 mm) and IK07 impact resistance. Operating altitude is 2000 m without derating; above that, derate per the manufacturer's curve.

Frequently asked questions

What is the breaking capacity of C10R42D100 at 415 V?

200 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. This is the R breaking capacity code.

What trip unit does C10R42D100 use?

A MicroLogic 2.2 electronic trip unit providing L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection. The rating is fixed at 100 A.

Where can I buy C10R42D100?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

MPN
C10R42D100