The thermal element handles the L curve (overload), the magnetic element handles the I curve (short-circuit); no earth-leakage module inside this variant.
Breaking capacity and fit
At 690 V AC it still holds 45 kA Icu, which covers most industrial line-to-line feeds. The 4-pole (4P) construction with neutral left handles three-phase plus neutral distribution panels; the neutral protection setting is fixed at 1 x Ir (4D), meaning the neutral pole tracks the phase protection.
Mounts flat on a backplate in horizontal or vertical orientation — no DIN-rail clip, so plan for a drilled panel or a subplate. Front connections top and bottom; 35 mm connection pitch matches standard busbar or cable-lug spacing.