The 3-pole (3P) configuration and 16 kA breaking capacity at 415 V AC (performance level E) mean it can safely interrupt fault currents up to that level on a 415 V distribution board, protecting downstream cables and loads. The TM-D trip gives fixed thermal and magnetic settings — no adjustment dials — so it's a straight swap-in for a distribution circuit where the load current is known and stable. Rated under EN/IEC 60947-2, this breaker is suitable for isolation (yes, per the standard), so it doubles as a visible-break disconnect in the panel. The IP40 front face and IK07 impact resistance mean it handles the usual panel environment — tools dropped during wiring won't crack the housing, and the toggle actuator stays protected against accidental contact.
The 9-module pitch (9 x 9 mm) matches the modular spacing used in Schneider distribution boards. Operating altitude is 2000 m without derating, up to 5000 m with derating. The grey (RAL 7016) housing is the standard colour for the ComPacT NSXm range.