Schneider Electric C11E4TM025L — Miniature Circuit Breakers (MCB)

Schneider Electric C11E4TM025L ComPacT NSXm 25A 4P MCCB, 16

MPNC11E4TM025L
Active

Schneider Electric ComPacT NSXm, circuit breaker, 25 A, 4P, thermal-magnetic TM-D trip unit, 16 kA at 415 V AC, IEC 60947-2.

$281.65 – $438.80Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11E4TM025L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11E4TM025L — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11E4TM025L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11E4TM025L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11E4TM025L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11E4TM025L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11E4TM025L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11E4TM025L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

25 A MCCB for distribution panels

The 4-pole version (4P) switches all four poles, with neutral on the left. IP40 front-face protection keeps tools and fingers out; IK07 impact resistance handles accidental panel-door strikes. Mounting is backplate with horizontal or vertical orientation — no DIN-rail clip on this frame, so budget for panel-mount hardware.

Termination and wiring

Front-face connection top and bottom via Everlink lugs. Wire range: 2.5…95 mm² rigid or stranded aluminium/copper; 2.5…70 mm² flexible copper. The 35 mm connection pitch with spreaders (27 mm without) matches standard busbar systems. Strip and torque per the manufacturer's published values — the lug design accepts both Cu and Al conductors without bi-metal washers, but aluminium terminations should be retorqued after thermal cycling.

Frequently asked questions

Where can I buy C11E4TM025L and how is it quoted?

The C11E4TM025L is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. For volume purchases or catalog punch-out setup, submit a sourcing request with your target quantity and delivery window.

What standards does C11E4TM025L comply with?

The C11E4TM025L is certified to EN/IEC 60947-2 for circuit-breaker performance and isolation suitability. It also meets pollution degree 3 per IEC 60664-1, IK07 per IEC 62262, and IP40 per IEC 60529.

What is the breaking capacity of C11E4TM025L?

The C11E4TM025L has a 16 kA breaking capacity at 415 V AC (performance level E per IEC 60947-2). This is the maximum fault current it can safely interrupt at that voltage without external current-limiting fuses.

MPN