Skip to main content
Schneider Electric C11E4TM040B — Miniature Circuit Breakers (MCB)

Schneider Electric C11E4TM040B ComPacT NSXm 40A 4P MCCB, 16k

MPNC11E4TM040B
Active

Schneider Electric ComPacT NSXm, 40 A, 4P, TM-D thermal-magnetic trip unit, 16 kA at 415 V AC, IP40, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11E4TM040B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11E4TM040B — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11E4TM040B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11E4TM040B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11E4TM040B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11E4TM040B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11E4TM040B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11E4TM040B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Built to EN/IEC 60947-2, with suitability for isolation marked on the device. The TM-D trip unit combines a thermal bimetal for overload protection and a magnetic coil for short-circuit protection — no electronics, no adjustment. For distribution duty (Category A), it's a fixed-trip, no-selectivity breaker sized for a 40 A feeder.

Breaking capacity and deployment

Front connection top and bottom, terminals accept compression lugs or busbars. 108 mm wide, 137 mm high, 80 mm deep; 12 module pitches at 9 mm. IK07 impact rating handles light knocks during installation.

Frequently asked questions

What is the breaking capacity of C11E4TM040B?

16 kA at 415 V AC, performance level E per IEC 60947-2. That is the maximum prospective fault current it can safely interrupt at that voltage.

What trip unit does C11E4TM040B use?

A TM-D thermal-magnetic trip unit rated 40 A at 40 °C. Fixed, non-interchangeable — overload protection via bimetal, short-circuit via magnetic coil.

Where can I buy C11E4TM040B?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN