Built to EN/IEC 60947-2, with suitability for isolation marked on the device. The TM-D trip unit combines a thermal bimetal for overload protection and a magnetic coil for short-circuit protection — no electronics, no adjustment. For distribution duty (Category A), it's a fixed-trip, no-selectivity breaker sized for a 40 A feeder.
Breaking capacity and deployment
Front connection top and bottom, terminals accept compression lugs or busbars. 108 mm wide, 137 mm high, 80 mm deep; 12 module pitches at 9 mm. IK07 impact rating handles light knocks during installation.