It is designed for backplate mounting and front-connect wiring via Everlink lugs accepting up to 95 mm² rigid or 70 mm² flexible copper.
The TM-D trip unit provides thermal protection for overloads and magnetic protection for short-circuits, with a fixed magnetic threshold. Category A utilisation (EN/IEC 60947-2) means it is not intended for motor starting — it is a distribution breaker, not a motor-protective device.
Mounts flat on a backplate, either horizontally or vertically. The 108 mm width (12 module pitches at 9 mm) and 137 mm height fit standard distribution board cutouts. Connection pitch is 35 mm with spreaders, 27 mm without. IP40 protection means it is splash-proof but not washdown-rated — keep it inside the enclosure, not in the food zone. The grey RAL 7016 finish is the standard industrial colour.