Skip to main content
Schneider Electric C11F4TM050B — Miniature Circuit Breakers (MCB)

Schneider C11F4TM050B ComPacT NSXm 4P 50A MCCB, 36 kA 415V

MPNC11F4TM050B
Active

Schneider Electric ComPacT NSXm, C11F4TM050B, 4P 50A thermal-magnetic MCCB, 36 kA at 415 V AC, IP40, current production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11F4TM050B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11F4TM050B — Ratings
ParameterValue
Rated current (In)50 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11F4TM050B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11F4TM050B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11F4TM050B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11F4TM050B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11F4TM050B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
C11F4TM050B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

What the ratings mean for fit

The C11F4TM050B: The 50 A rating at 40 °C is the continuous current the breaker carries without tripping in a 40 °C ambient — standard for most enclosed distribution panels. The 36 kA at 415 V AC is the maximum prospective fault current it can safely interrupt; that F-class performance covers most commercial and light industrial service entrances where the available fault current stays under that level. The 4P (four-pole) configuration with neutral left is typical for TN or TT systems where the neutral is switched and protected. Thermal-magnetic trip (TM-D) means it responds to sustained overloads (thermal element) and short-circuits (magnetic element) with a fixed magnetic threshold — no electronic adjustment, which simplifies specification for fixed-load feeders.

Mounting and integration

Mounts on a backplate in horizontal or vertical orientation, flat on the back. The 108 mm width, 137 mm height, and 80 mm depth occupy 12 module pitches of 9 mm. Front connections top and bottom accept compression lugs or busbars. IP40 enclosure protection means it is protected against tools and small wires >1 mm — fine for a clean indoor panel; no washdown rating. Pollution degree 3 per IEC 60664-1 covers conductive pollution typical in industrial control rooms.

Frequently asked questions

How do I get current pricing and availability for C11F4TM050B?

The C11F4TM050B is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current pricing and availability at the time of order.

What is the breaking capacity of C11F4TM050B?

The C11F4TM050B carries a 36 kA interrupting capacity at 415 V AC (performance level F) per EN/IEC 60947-2.

What standards does C11F4TM050B comply with?

The C11F4TM050B is certified to EN/IEC 60947-2 and carries suitability for isolation per that standard. Pollution degree 3 per IEC 60664-1 and IK07 impact resistance per IEC 62262.

MPN