Skip to main content
Schneider Electric C11F4TM040B — Miniature Circuit Breakers (MCB)

Schneider Electric C11F4TM040B ComPacT NSXm, 40 A, 36 kA 415

MPNC11F4TM040B
Active

Schneider Electric ComPacT NSXm, C11F4TM040B, 40 A thermal-magnetic MCCB, 4P, 36 kA at 415 V AC, IP40, grey RAL 7016.

$518.67Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11F4TM040B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11F4TM040B — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11F4TM040B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11F4TM040B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11F4TM040B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11F4TM040B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11F4TM040B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
C11F4TM040B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C11F4TM040B is a Schneider Electric ComPacT NSXm moulded-case circuit breaker, 40 A rated current with a thermal-magnetic TM-D trip unit. Four-pole, 36 kA breaking capacity at 415 V AC — that's the F performance level, meaning it clears faults up to that level without upstream coordination issues in a distribution panel. Mounts on a backplate, 108 mm wide, 12-module pitch at 9 mm per module.

What the ratings mean for fit

40 A at 40 °C is the continuous current rating — don't push it past that in a warm panel. The TM-D trip unit gives thermal-magnetic protection: thermal for overloads, magnetic for short-circuits. Category A utilisation means it's not intended for cascading selectivity with downstream breakers; you coordinate it at the panel level. 36 kA at 415 V AC is the interrupting rating — the breaker can safely clear a fault up to that available current. In a 400 V distribution board with a transformer sized for 36 kA or less, this holds. Above that, you need a higher-rated frame. Pollution degree 3 and overvoltage category III suit it for industrial fixed-installation panels, not residential. IP40 front face, IK07 impact resistance — it's protected against tools and wires >1 mm, but not washdown. Keep it inside the enclosure, not on the machine exterior. The flag indicator on top shows green when auxiliary contacts are present — a quick visual for panel walk-downs.

Where it goes

This is a distribution breaker for a 400 V AC, 50/60 Hz three-phase panel. Four-pole, so it switches all three phases plus neutral. Neutral fixed left, front connections top and bottom — compression lug or busbar. Mounts flat on a backplate, horizontal or vertical. 80 mm deep, 137 mm tall — fits standard distribution board cutouts.

Lifecycle and sourcing

Listed as current production. No end-of-life notice on record. Sourced to order against an RFQ — we confirm availability and current pricing at quote time. For volume or scheduled releases, submit the C11F4TM040B line item and we'll quote firm.

Frequently asked questions

What is the breaking capacity of C11F4TM040B?

36 kA at 415 V AC, performance level F. That's the maximum fault current it can interrupt at that voltage.

What standards does C11F4TM040B comply with?

EN/IEC 60947-2 for low-voltage switchgear and controlgear. Suitability for isolation is confirmed per that standard.

MPN