Skip to main content
Schneider Electric C11F4TM063B — Miniature Circuit Breakers (MCB)

Schneider Electric C11F4TM063B ComPacT NSXm 63A 4P MCCB, 36

MPNC11F4TM063B
Active

Schneider Electric, ComPacT NSXm, MCCB, C11F4TM063B, 63A 4P, 36 kA 415 V AC, thermal-magnetic TM-D trip unit.

$518.67Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11F4TM063B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11F4TM063B — Ratings
ParameterValue
Rated current (In)63 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11F4TM063B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11F4TM063B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11F4TM063B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11F4TM063B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11F4TM063B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
C11F4TM063B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

63 A, 4-pole MCCB with TM-D trip unit

The Schneider Electric C11F4TM063B is a ComPacT NSXm 63F molded-case circuit breaker rated 63 A at 40 °C with four poles (4P), a thermal-magnetic TM-D trip unit, and a 36 kA interrupting capacity at 415 V AC (performance level F). This is a distribution-grade MCCB built to EN/IEC 60947-2, Category A — it is not current-limiting by design, so coordination studies should account for full let-through on bolted faults below its rated breaking capacity.

The 4P configuration switches all four poles (three phases plus neutral), with the neutral pole on the left side of the breaker.

The 108 mm width occupies 12 module pitches of 9 mm. Connection is front-facing via compression lugs or busbars; connection pitch is 35 mm with spreaders, 27 mm without. The toggle handle provides manual control, and a green flag signals presence of auxiliary contacts. IP40 enclosure protection and IK07 impact resistance suit it for panel-mount applications in clean industrial environments.

Frequently asked questions

How do I get current pricing and availability for C11F4TM063B?

Submit an RFQ for this order code; pricing and stock are confirmed at quote time through independent distribution channels.

What standards does C11F4TM063B comply with?

It is certified to EN/IEC 60947-2 for molded-case circuit breakers, with suitability for isolation confirmed per that standard.

What is the interrupting rating of C11F4TM063B?

Performance level F: 36 kA at 415 V AC. This is the Icu (ultimate short-circuit breaking capacity) per IEC 60947-2.

MPN