Schneider Electric C11F6TM100L — Miniature Circuit Breakers (MCB)

Schneider Electric C11F6TM100L ComPacT NSXm 100A 4P MCCB, 36

MPNC11F6TM100L
Active

Schneider Electric ComPacT NSXm, 100 A, 4P, TM-D thermal-magnetic trip, 36 kA at 415 V AC, EN/IEC 60947-2.

$245.43Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11F6TM100L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11F6TM100L — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11F6TM100L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C11F6TM100L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11F6TM100L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11F6TM100L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11F6TM100L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C11F6TM100L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C11F6TM100L is a ComPacT NSXm 160F frame moulded-case circuit breaker with a 100 A thermal-magnetic TM-D trip unit, 4 poles, and a 36 kA interrupting rating at 415 V AC.

That is an F-class performance level. The TM-D trip unit is thermal-magnetic: the thermal bimetal handles overloads (slow trip on sustained overcurrent), and the magnetic solenoid handles short-circuits (instantaneous trip above a set threshold). No electronic adjustment or zone selective interlocking here — it's a fixed-curve device. The neutral pole is on the left and is switched — not solid — so it's suitable for TN or TT systems where you need to isolate the neutral. If your system is a corner-grounded delta or you only need 3-pole switching, this isn't the variant.

The 9 mm pitch footprint is 12 modules wide — that's 108 mm of DIN-rail space if you're laying out a panel. Front connections both top and bottom with Everlink lugs that accept 2.5 to 95 mm² rigid or stranded aluminium/copper, or 2.5 to 70 mm² flexible copper. That's a wide wire range — covers everything from a 16 mm² feeder to a 70 mm² main.

Frequently asked questions

What is the breaking capacity of C11F6TM100L?

36 kA at 415 V AC, which is the F-class performance level per the NSXm 160F frame.

What standards does this breaker comply with?

EN/IEC 60947-2 for low-voltage switchgear and controlgear. It also carries suitability for isolation per that standard.

MPN