50 A MCCB with 70 kA interrupting rating
Mounting and connection
Mounts on a backplate in horizontal or vertical orientation. Front-facing Everlink lugs accept rigid or stranded aluminium/copper up to 95 mm² (70 mm² flexible), which covers most panel feeder and subfeed applications. The 9-module pitch (81 mm wide) fits standard enclosure cutouts.
Durability and duty
Rated for 20,000 mechanical cycles and 20,000 electrical cycles at 440 V In/2 (10,000 at full In). That aligns with typical panel-switchgear life for distribution duty — not for frequent motor starting, but fine for branch-circuit protection where switching is occasional.