Skip to main content
Schneider Electric C11H3TM080B — Miniature Circuit Breakers (MCB)

Schneider Electric C11H3TM080B ComPacT NSXm MCCB, 80 A, 70 k

MPNC11H3TM080B
Active

Schneider Electric ComPacT NSXm, C11H3TM080B, 3-pole MCCB, 80 A TM-D trip unit, 70 kA at 415 V AC, IP40, grey RAL 7016.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H3TM080B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H3TM080B — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H3TM080B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C11H3TM080B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches9 module
C11H3TM080B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H3TM080B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H3TM080B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C11H3TM080B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

80 A MCCB with 70 kA breaking capacity — ComPacT NSXm

The IP40 enclosure rating and IK07 impact resistance cover it for general indoor switchboard installation — no washdown protection, so keep it out of hose-down zones.

Trip unit and duty ratings

At 80 A, the power dissipation per pole is 5.8 W, so a three-pole breaker dissipates about 17.4 W — factor that into enclosure ventilation if the panel is densely packed. Electrical durability is 20,000 cycles at 440 V at In/2 and 10,000 cycles at In — sufficient for a distribution breaker that sees infrequent switching. Mechanical durability matches at 20,000 cycles. The breaker is category A (no intentional short-time delay), so it trips instantaneously on short-circuit; coordinate downstream with current-limiting devices if you need selectivity.

The 81 mm width occupies 9 module pitches on a standard DIN cut-out. Connections are front-facing, accepting compression lugs or busbars with a 35 mm pitch (27 mm without spreaders). The grey RAL 7016 housing is the standard industrial finish for the NSXm range.

Frequently asked questions

What is the breaking capacity of C11H3TM080B?

The C11H3TM080B is rated performance level H, providing 70 kA breaking capacity at 415 V AC per IEC 60947-2.

What is the trip unit type and rating?

It uses a TM-D thermal-magnetic trip unit rated at 80 A at 40 °C.

Where can I buy C11H3TM080B and get current pricing?

The C11H3TM080B is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What standards does C11H3TM080B comply with?

It complies with EN/IEC 60947-2 and is suitable for isolation per that standard. Pollution degree 3 per IEC 60664-1 and overvoltage category III are specified.

MPN
C11H3TM080B