Skip to main content
Schneider Electric C11N6TM016B — Miniature Circuit Breakers (MCB)

Schneider Electric C11N6TM016B ComPacT NSXm 16A 4P MCCB, 50

MPNC11N6TM016B
Active

Schneider Electric ComPacT NSXm, 16 A, 4P, thermal-magnetic trip unit TM-D, 50 kA 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11N6TM016B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11N6TM016B — Ratings
ParameterValue
Rated current (In)16 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11N6TM016B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11N6TM016B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11N6TM016B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11N6TM016B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11N6TM016B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity90 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11N6TM016B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The thermal-magnetic TM-D trip gives you an instantaneous magnetic trip for short-circuits and a thermal bimetal for overloads; no electronic adjustment, so it's a fixed-curve device suited for straightforward distribution or feeder protection where you don't need field-adjustable settings. Mechanical durability of 20,000 cycles and electrical durability of 20,000 cycles at 440 V In/2 (half rated current) or 10,000 cycles at full rated current — that's the life you get before the contacts wear out. For a distribution breaker that operates maybe a few times a year, that's effectively the life of the panel. For a frequent-switching application like a motor disconnect, you'd want a contactor instead.

The 108 mm width, 137 mm height, and 80 mm depth fit a standard 12-module 9 mm pitch DIN-rail footprint. The 35 mm connection pitch with spreaders (27 mm without) tells you the busbar hole spacing you need.

Frequently asked questions

What are the key ratings for C11N6TM016B?

16 A rated current at 40 °C, 4 poles, thermal-magnetic TM-D trip unit, 50 kA interrupting capacity at 415 V AC (performance level N), conforming to EN/IEC 60947-2.

Where can I buy C11N6TM016B and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What compliance standards does C11N6TM016B meet?

It conforms to EN/IEC 60947-2 for low-voltage switchgear and controlgear. Suitability for isolation is confirmed per that standard. Pollution degree 3 per IEC 60664-1, overvoltage category III.

MPN
C11N6TM016B