Skip to main content
Schneider Electric C11N6TM025L — Miniature Circuit Breakers (MCB)

Schneider C11N6TM025L ComPacT NSXm 25A 4P MCCB, 50kA 415V

MPNC11N6TM025L
Active

Schneider Electric ComPacT NSXm, TM-D 25 A, 4P, 50 kA 415 V AC, thermal-magnetic circuit breaker, Grey (RAL 7016).

$255.69Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11N6TM025L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11N6TM025L — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11N6TM025L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11N6TM025L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11N6TM025L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11N6TM025L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11N6TM025L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity90 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11N6TM025L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

This is the distribution-grade version — Category A utilisation, no earth-leakage module, designed for panelboard and sub-distribution duty where you need isolation capability (it's certified for isolation per IEC 60947-2).

Termination and wiring notes

Accepts 2.5 to 95 mm² rigid or stranded aluminium/copper, or 2.5 to 70 mm² flexible copper. Connection pitch is 35 mm with spreaders, 27 mm without. Neutral is on the left. The flag indicator (green) shows presence of auxiliary contacts — useful for panel builders who need a visual check without opening the cover.

Frequently asked questions

What is the breaking capacity of C11N6TM025L?

50 kA at 415 V AC (performance level N). That's the short-circuit breaking capacity per EN/IEC 60947-2.

Where can I buy C11N6TM025L and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for C11N6TM025L?

The breaker is certified to EN/IEC 60947-2, carries IP40 and IK07 ratings, and is suitable for isolation per the same standard. RoHS, REACH, and CE/UKCA declarations are standard for Schneider's ComPacT range — request them with your RFQ.

MPN
C11N6TM025L