125 A, 16 kA — panel integration note
The 4P configuration (switched neutral left) suits three-phase + N distribution boards where the neutral must be protected.
IP40 front face keeps out tools and wires ≥1 mm; IK07 impact resistance handles accidental tool drops during commissioning. The lifecycle status is current — this is an active catalogue item, not a phase-out or NRND line.
Mounts flat on a backplate (horizontal or vertical), 12-module 9 mm pitch width (108 mm wide, 137 mm high, 80 mm deep). Connection terminals accept compression lugs or busbars, with a 35 mm pitch when using spreaders, 27 mm without. The toggle control is manual; auxiliary contact presence is indicated by a green flag.
Durability and environment
Electrical endurance: 20,000 cycles at 440 V at In/2, 10,000 cycles at 440 V at In. Mechanical durability matches at 20,000 cycles. Relative humidity range 0–95 % non-condensing. Overvoltage category III — suitable for fixed-installation distribution boards downstream of the main incoming supply.