Skip to main content
Schneider Electric C12E4TM160L — Miniature Circuit Breakers (MCB)

Schneider Electric C12E4TM160L ComPacT NSXm 160A 4P MCCB, 16

MPNC12E4TM160L
Active

Schneider Electric ComPacT NSXm, C12E4TM160L, 160 A at 40 °C, 4P, 16 kA at 415 V AC, thermal-magnetic TM-D trip unit, EN/IEC 60947-2.

$347.57Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C12E4TM160L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C12E4TM160L — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C12E4TM160L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C12E4TM160L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C12E4TM160L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C12E4TM160L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C12E4TM160L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C12E4TM160L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C12E4TM160L is a ComPacT NSXm moulded-case circuit breaker (MCCB) rated 160 A at 40 °C with a 4-pole (4P) configuration and a thermal-magnetic TM-D trip unit.

The TM-D thermal-magnetic trip unit gives you fixed thermal and magnetic settings — no adjustment dials, which simplifies ordering and stocking but means you must size the breaker to the load exactly. The 4P version switches all four poles, including the neutral, which is typical for TN-S or TT systems where you want full isolation. Mechanical durability is 20,000 cycles, electrical durability 20,000 cycles at 440 V In/2 and 10,000 cycles at 440 V In — so it's built for distribution duty (occasional switching), not for frequent motor starting. The Everlink lug terminals accept 2.5–70 mm² flexible copper or 2.5–95 mm² rigid/stranded copper. That's a wide wire range — you can land a 95 mm² feeder on the line side and tap a 2.5 mm² branch on the load side without adapters. The 12-module 9 mm pitch (108 mm wide) gives you a sense of the panel space it occupies.

Frequently asked questions

How do I get current pricing and availability for C12E4TM160L?

Pricing and live availability are confirmed at quote time. Submit an RFQ for C12E4TM160L and we will respond with current pricing and lead time.

What is the breaking capacity of C12E4TM160L?

The C12E4TM160L has a performance level E breaking capacity of 16 kA at 415 V AC.

What standards does C12E4TM160L comply with?

It complies with EN/IEC 60947-2 and is suitable for isolation per that standard.

MPN