Specifications

C12F4TM160L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C12F4TM160L — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C12F4TM160L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C12F4TM160L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C12F4TM160L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C12F4TM160L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C12F4TM160L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C12F4TM160L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

This is a distribution-grade MCCB, not a motor-protective device — the TM-D curve is sized for cable and busbar protection in commercial and industrial power panels.

That puts it in the F performance tier, appropriate for distribution boards with moderate fault levels.

Panel integration

Mounts on a backplate, not a DIN rail — the 108 mm width and 137 mm height fill a 12-module pitch at 9 mm per module. Connection is front-to-front (both line and load terminals on the front face), which simplifies busbar and cable routing in a distribution panel. Everlink lug terminals accept 2.5–70 mm² flexible copper or 2.5–95 mm² rigid/stranded copper per pole.

Frequently asked questions

What is the breaking capacity of C12F4TM160L?

The rated ultimate short-circuit breaking capacity (Icu) is 36 kA at 415 V AC, which corresponds to the F performance level in the ComPacT NSXm range. This is the maximum fault current the breaker can safely interrupt.