Skip to main content
Schneider Electric C12H4TM160L — Miniature Circuit Breakers (MCB)

Schneider Electric C12H4TM160L ComPacT NSXm, 160A 4P 70kA

MPNC12H4TM160L
Active

Schneider Electric ComPacT NSXm, C12H4TM160L, 4P 160A thermal-magnetic MCCB, 70kA at 415V AC, IP40, grey RAL 7016.

$452.11Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C12H4TM160L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C12H4TM160L — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C12H4TM160L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C12H4TM160L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C12H4TM160L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C12H4TM160L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C12H4TM160L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C12H4TM160L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Where it fits and how it mounts

Dimensions 108 mm wide × 137 mm high × 80 mm deep — 12 module pitches at 9 mm. Connection terminals are Everlink lugs: front-connect both sides, accepting 2.5…70 mm² flexible copper or 2.5…95 mm² rigid/stranded. Neutral on the left. IP40 enclosure, IK07 impact rating — suited for panel interiors where occasional tool contact is expected, not washdown zones.

Current production stage — no end-of-life notice on this code. No official successor listed; the ComPacT NSXm family is the active generation.

Frequently asked questions

What compliance documentation does this brand provide for C12H4TM160L?

The breaker is certified to EN/IEC 60947-2 and carries an IEC 60947-2 isolation suitability marking. Pollution degree 3 per IEC 60664-1 and IK07 per IEC 62262 are also documented. RoHS and REACH declarations are typically available from the manufacturer's documentation portal for the ComPacT NSXm series.

Where can I buy C12H4TM160L?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume and delivery window.

MPN
C12H4TM160L