Skip to main content
Schneider Electric C10H4TM040C — Miniature Circuit Breakers (MCB)

C10H4TM040C ComPacT NSX100H 40A MCCB, 100kA 240V

MPNC10H4TM040C
Active

Schneider Electric ComPacT NSX100H, 40 A, 4P, thermal-magnetic (TM-D) MCCB, 100 kA Icu at 240 V AC, 70 kA at 415 V, toggle control, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10H4TM040C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10H4TM040C — Ratings
ParameterValue
Rated current (In)40 A at 50 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10H4TM040C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10H4TM040C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10H4TM040C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10H4TM040C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10H4TM040C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10H4TM040C is a 40 A, 4-pole ComPacT NSX100H moulded-case circuit breaker from Schneider Electric's current-production ComPacT NSX line. The headline breaking capacity is 100 kA Icu at 220/240 V AC, 70 kA at 380/415 V, and still 10 kA at 660/690 V — all per IEC 60947-2. That 'H' suffix in NSX100H means the high-breaking version; in a 415 V distribution board this breaker clears a 70 kA fault without upstream fuses needing to operate, which simplifies coordination studies and lets you keep the same SCCR downstream.

Backplate-mounted, 140 mm wide × 161 mm high × 86 mm deep. Front connections both top and bottom. Neutral on the left, 4-pole with neutral protection set at 1 × Ir (full-rated neutral). Five accessory slots available for auxiliary contacts, shunt trips, or under-voltage releases. IP40 finger protection on the front face; IK07 impact resistance per IEC 62262.

Mechanical endurance is 50,000 cycles. Electrical endurance varies with load: 50,000 cycles at 440 V at half rated current, 30,000 at full rated current, and 10,000 at 690 V full load. Utilisation category A (non-frequent switching, typical for distribution rather than motor starting).

Frequently asked questions

What is the breaking capacity of C10H4TM040C at 415 V?

70 kA Icu at 380/415 V AC per IEC 60947-2. At 240 V it reaches 100 kA; at 690 V it still holds 10 kA.

Where can I buy C10H4TM040C and how do I get a price?

This part is sourced to order against an RFQ through independent distribution channels. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock or price figures are published here.

What compliance documentation does Schneider provide for C10H4TM040C?

The breaker is certified to EN/IEC 60947-2, carries IP40 and IK07 ratings, and is suitable for isolation per that standard. Specific RoHS, REACH, or UL documentation should be requested at quote time as it varies by manufacturing batch and destination.

MPN
C10H4TM040C