Skip to main content
Schneider Electric C10H4TM025C — Miniature Circuit Breakers (MCB)

C10H4TM025C ComPacT NSX100H 25A 4P MCCB, 70kA 415V

MPNC10H4TM025C
Active

Schneider Electric ComPacT NSX100H, 25 A, 4-pole, thermal-magnetic TM-D, 70 kA at 415 V AC, backplate mount, IP40, IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10H4TM025C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10H4TM025C — Ratings
ParameterValue
Rated current (In)25 A at 50 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10H4TM025C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10H4TM025C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10H4TM025C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10H4TM025C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10H4TM025C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10H4TM025C is a 25 A, 4-pole ComPacT NSX100H moulded-case circuit breaker (MCCB) from the Schneider Electric ComPacT range. It uses a thermal-magnetic TM-D trip unit for overload (L) and short-circuit (I) protection. The H breaking capacity code means 70 kA Icu at 415 V AC, 50/60 Hz, per IEC 60947-2 — enough to handle high-fault distribution panels without cascading upstream.

Trip unit rating is 25 A at 50 °C, so this breaker carries a 25 A continuous load in a 50 °C ambient. Breaking capacity is 100 kA Icu at 240 V AC, 70 kA at 415 V, 65 kA at 440 V, 50 kA at 500 V, 35 kA at 525 V, and 10 kA at 690 V — the H frame is sized for high-fault industrial distribution. Mechanical durability is 50,000 cycles; electrical durability is 50,000 cycles at 440 V at half rated current, 30,000 at full rated current. That's a solid service life for a distribution MCCB in a panel that sees regular switching.

Mounts on a backplate, flat on the back, in horizontal or vertical orientation. IP40 enclosure protection keeps out tools and wires; IK07 impact resistance handles accidental bumps during installation.

MPN