Schneider Electric C160H3WM — Miniature Circuit Breakers (MCB)

C160H3WM ComPacT NS1600H 1600A 3P Drawout Frame, 70kA at 415

MPNC160H3WM
Active

Schneider Electric ComPacT NS630b...1600 new generation, C160H3WM, basic frame, 1600 A, 3P, drawout, manually operated, without control unit, 70 kA Icu at 415 V AC.

$2,734.85 – $7,344.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C160H3WM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C160H3WM — Ratings
ParameterValue
Rated current (In)1600 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C160H3WM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)1000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 2000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 2000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C160H3WM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeWithdrawable
Control typeManually operated
C160H3WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C160H3WM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

It is manually operated and designed for distribution applications. The 70 kA Icu at 415 V AC (85 kA at 240 V, 65 kA at 440 V, 50 kA at 500/525 V, 42 kA at 690 V) means this frame handles high-fault-current mains without upstream cascading, keeping selectivity intact on a 415 V bus. Rated 1600 A at 50 °C ambient, so it holds full ampacity even in a warm switchroom.

The 19.2 kA Icw for 1 second (short-time withstand) means this frame can carry through a delayed trip coordination band, essential for selective coordination on a main breaker. Withdrawable mounting (drawout) lets you rack the frame out for safe maintenance without unbolting bus connections — a time-saver on a live panel.

Integration notes

Dimensions: 260 mm H × 236 mm W × 147 mm D. IP40 front face, IK07 impact rating. Pollution degree 3 per IEC 60947 — suitable for industrial switchboards where conductive dust may be present. Class II insulation on the front face means no protective-earth connection required on the operator interface.

Frequently asked questions

Where can I buy C160H3WM?

The C160H3WM is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is C160H3WM's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The service breaking capacity (Ics) at the same voltage is 37 kA.

Does C160H3WM include a trip unit?

No. This is a basic frame without protection (no control unit). You must add a separate Micrologic trip unit for overcurrent protection.

What compliance documentation does Schneider provide for C160H3WM?

The frame is designed and tested to IEC 60947-2, with suitability for isolation per EN/IEC 60947-2. Pollution degree 3, overvoltage category III, and Class II insulation on the front face. Specific RoHS/REACH/UL declarations are available on request from the manufacturer.

MPN