Schneider Electric C160H35AFM — Miniature Circuit Breakers (MCB)

Schneider Electric C160H35AFM ComPacT NS, 1600 A, 85 kA

MPNC160H35AFM
Active

Schneider Electric, ComPacT NS new generation, C160H35AFM, 3P 1600 A MCCB, 85 kA Icu at 240 V AC, MicroLogic 5.0 A electronic trip unit, fixed mount, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C160H35AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C160H35AFM — Ratings
ParameterValue
Rated current (In)1600 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C160H35AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C160H35AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C160H35AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C160H35AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C160H35AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The Schneider Electric C160H35AFM is a ComPacT NS new generation 3-pole MCCB, rated 1600 A at 50 °C with a MicroLogic 5.0 A electronic trip unit. It carries an 85 kA Icu breaking capacity at 240 V AC, 70 kA at 415 V AC, and 42 kA at 690 V AC per IEC 60947-2 — that 70 kA at 415 V is the H-code rating you see on the nameplate. The trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous) protection curves, all adjustable through the LCD display. This is a manually operated, fixed-mount breaker designed for distribution duty, not motor-starting cycles.

The 1600 A frame at 50 °C is the continuous current rating — no derating needed at that ambient, but above 50 °C you follow the curve in the manual.

Integration notes

Fixed-mount, backplate-supported — no DIN-rail adapter. The 210 mm width, 327 mm height, and 147 mm depth fit a standard distribution section; connection pitch is 70 mm. The LCD display and four red fault LEDs plus one yellow overload LED give local diagnostics without opening the door. Mechanical durability is 10,000 cycles; electrical durability varies by voltage and current — 1,000 cycles at 690 V In, 2,000 at 690 V In/2, 2,000 at 440 V In, 5,000 at 440 V In/2.

IK07 impact resistance per EN 50102. IP40 per IEC 60529. Operating altitude up to 2,000 m without derating, 2,000–5,000 m with derating. Relative humidity 0–95 %. No earth-leakage protection built in — that's a separate accessory or upstream device.

Frequently asked questions

What is C160H35AFM's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. This is the H-code rating (70 kA 415 V AC) marked on the breaker.

What trip unit does C160H35AFM use?

A MicroLogic 5.0 A electronic trip unit with L, S, and I protection curves — adjustable via the front-panel LCD display.

Where can I buy C160H35AFM and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is listed here.

What compliance standards does C160H35AFM meet?

EN/IEC 60947-2, IK07 per EN 50102, IP40 per IEC 60529. Pollution degree 3, overvoltage category III.

MPN
C160H35AFM