Skip to main content
Schneider Electric C160H32EFM — Miniature Circuit Breakers (MCB)

Schneider Electric C160H32EFM ComPacT NS MCCB, 1600 A, 70 kA

MPNC160H32EFM
Active

Schneider Electric ComPacT NS new generation, C160H32EFM, 3P fixed MCCB, 1600 A at 50 °C, 70 kA Icu at 415 V AC, MicroLogic 2.0 E electronic trip unit, LSI protection.

$3,484.81Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C160H32EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C160H32EFM — Ratings
ParameterValue
Rated current (In)1600 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C160H32EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C160H32EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C160H32EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C160H32EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C160H32EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The C160H32EFM is a 3-pole fixed-mount ComPacT NS new generation MCCB rated 1600 A at 50 °C, carrying a MicroLogic 2.0 E electronic trip unit with L (long-time overload) and I (instantaneous short-circuit) protection curves. The 74 W power loss at rated current matters for enclosure thermal budgeting; plan ventilation accordingly. The 1600 A frame covers main incoming feeders or large bus risers in industrial and commercial switchboards. Fixed mounting on a backplate with front connections top and bottom keeps the wiring pattern predictable for panel builders.

The 85 kA Icu at 240 V and 70 kA at 415 V give the C160H32EFM headroom for high-available-fault installations. The 65 kA at 440 V and 50 kA at 500/525 V still cover most industrial service entrances. At 660/690 V it holds 42 kA — useful for 600 V class systems. These ratings conform to IEC 60947-2 Category B, meaning the breaker is fully selective with downstream devices under short-circuit conditions. The MicroLogic 2.0 E trip unit provides LSI protection via electronic sensing. Thermal memory holds for 20 minutes after a trip, preventing immediate reclose on a still-hot conductor. The LCD display shows measured values and fault type, and the four red LEDs indicate the fault cause — overload, short-circuit, or ground fault (though this unit ships without earth-leakage protection).

Fixed mounting on a backplate with 70 mm connection pitch. Front connections both top and bottom. Dimensions: 327 mm high, 210 mm wide, 147 mm deep. IK07 impact resistance handles incidental contact in a panel. Manually operated with an LCD display for local metering and energy measurement. The electronic trip unit draws power from the line side — no auxiliary supply needed for basic protection.

Frequently asked questions

What is the breaking capacity of C160H32EFM at 415 V?

The C160H32EFM delivers 70 kA Icu at 380/415 V AC 50/60 Hz, conforming to IEC 60947-2. This is the H breaking capacity code.

What trip unit does C160H32EFM use?

It uses the MicroLogic 2.0 E electronic trip unit with L (long-time overload) and I (instantaneous short-circuit) protection. It does not include earth-leakage protection.

MPN
C160H32EFM