Skip to main content
Schneider Electric C16B4TM100C — Miniature Circuit Breakers (MCB)

Schneider C16B4TM100C ComPacT NSX160B MCCB, 100 A, 4P

MPNC16B4TM100C
Active

Schneider Electric ComPacT NSX160B, C16B4TM100C, 100 A thermal-magnetic MCCB, 4 poles, 40 kA Icu at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16B4TM100C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16B4TM100C — Ratings
ParameterValue
Rated current (In)100 A at 50 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16B4TM100C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16B4TM100C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16B4TM100C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16B4TM100C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16B4TM100C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It is a 4-pole, 4-protected-pole device (neutral protection set at 1 x Ir, 4D) rated for AC networks at 50/60 Hz. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection in one compact package. Rated 100 A at 50 °C, this breaker is sized for distribution and feeder circuits in commercial and industrial panelboards. The 40 kA Icu at 240 V AC (25 kA at 415 V, 20 kA at 440 V, 15 kA at 500 V) gives it solid fault-interrupting capability for most low-voltage distribution applications — enough headroom to coordinate with downstream branch breakers without cascading failure. Pollution degree 3 (IEC 60664-1) means it handles conductive dust and humidity typical of industrial enclosures without tracking.

Front-front connections — line and load both terminate on the front face, which simplifies busbar routing in a panel but means you need clearance in front for cable entry. Dimensions: 161 mm H × 140 mm W × 86 mm D. Connection pitch is 35 mm per pole, standard for 4-pole MCCB busbar systems. IP40 front face (finger-safe), IK07 impact rating. Suitable for enclosure mounting where the operator interface is behind a door. Relative humidity 0–95 % non-condensing. Overvoltage category III — suitable for fixed-installation distribution boards.

Durability and endurance

Mechanical endurance: 40,000 operations. Electrical endurance varies by load: 40,000 cycles at 440 V at half rated current (In/2), 20,000 cycles at full rated current (In) at 440 V, 15,000 cycles at 690 V In/2, and 7,500 cycles at 690 V In. These numbers matter for frequent-switching applications like lighting or motor feeder panels where the breaker cycles regularly.

Frequently asked questions

What is the breaking capacity of C16B4TM100C?

40 kA Icu at 220/240 V AC, 25 kA at 380/415 V, 20 kA at 440 V, and 15 kA at 500 V, all per IEC 60947-2. The breaking capacity code is B (25 kA at 415 V).

What standards does C16B4TM100C comply with?

EN/IEC 60947-2 for circuit-breaker performance and safety. It also meets IEC 60664-1 pollution degree 3, IEC 60529 IP40, and IEC 62262 IK07.

MPN