The C16B4TM125C is a Schneider Electric ComPacT NSX160B moulded-case circuit breaker, 4-pole, rated 125 A at 50 °C with a TM-D thermal-magnetic trip unit. The TM-D provides fixed overload (L) and short-circuit (I) protection — no adjustment dials, so the trip curve is set at the factory for distribution duty. The 25 kA Icu at 415 V AC (40 kA at 240 V) is the interrupting rating under IEC 60947-2; at 415 V it clears a 25 kA fault without damage to the breaker, which is the figure that governs selectivity coordination in a 400 V panel. The 125 A frame means it fits as a main or feeder breaker in a distribution board, not a motor-protective device — utilisation category A confirms it is not intended for frequent switching of motor starts.
Deployment context
The IP40 enclosure is suitable for dry indoor panels; the IK07 impact rating means it withstands light tool drops during installation.